Padmount Transformers come in a wide variety of electrical and mechanical configurations. They may be offered in any voltage, phase or frequency required.
A Padmount Transformer is mounted on a 'pad' foundation with high and low voltage underground cables entering from below directly into the terminal compartments, which are a part of the transformer housing. Padmount transformers are specially designed for ease of installation and reliability in public areas, where a tamper-proof design is required.
Liquid-filled Transformers Padmount type (75 to 15000 kVA)
Benefits of Pacific Crest Transformer design
- A Padmount Transformer is designed for distribution and specialty (dedicated load) applications, in public access areas where security and public safety are of premier importance
- Pacific Crest Transformers are also designed for ease of installation and first cost savings
- Integral fault protection reduces outage time
- Single-phase or three-phase designs are available,depending on load requirements
- Internal loadbreak switches can be used as loadbreak devices or as a sectionalizing switch to locate faults and isolate them
- Safe, dead-front construction or live front construction options are available
Application
- A Padmount Transformer is a single piece of equipment with integral HV and LV terminal chamber; it requires less space and makes installation simpler, less expensive and more aesthetic.
- This also means that costs associated with operation and maintenance are reduced.
- PCT's liquid-filled, Padmount Transformers are an ideal choice for commercial, industrial, and utility applications.
- All ratings are designed in accordance with applicable ANSI, NEMA and IEEE standards.
Product Scope
- Sizes from 75 kV through 10 MVA
- Voltages through 69 kV and 350 kV BIL
- Terminations designed to meet customers specific needs
Ratings
- kVA ratings - 75 kVA to 10000 kVA
- Primary Voltage - all voltages through 46 kV - 250 kV BIL
- Secondary Voltage - all voltages through 15 kV
- Frequency - 60Hz
- Temperature rise 65° C
- Consult factory for ratings not shown
Standard Features
- De-energized tapchanger if required
- Secondary spade connectors
- Primary clamp type eyebolt connectors
- Combination drain and sampler (750 kVA and above)
- Pressure test and upper filter press connection - 1" pipe plug
- NEMA two hole ground pad
- Corrosion resistant nameplate
- Provisions for jacking and lifting
- Base suitable for rolling or skidding
- Pressure relief valve
- Rugged steel plate tank reinforced with steel channel selections for strength and rigidity
- Undercoated base
- Door has three-point locking mechanism
- Externally clamped high and low voltage bushings
- Primary compartment accessible only after low voltage door is opened
- 1/2" liquid level plug
- Welded cover with handhole
Optional Features
Five-legged core for wye-wye connections
- 50 cycle
- 55/65° C temperature rise
- High fire point liquid
- Loop feed construction
- Dead front construction
- Lightning arrestors
- Dial type thermometer
- Liquid level gauge
- Pressure vacuum gauge
- Pressure vacuum gauge with bleeder
- Combination drain and sampler
- Pressure relief device
- Bay-o-net fuses
- Weak links
- Current limiting fuses
- Loadbreak oil switch(es)
- Loadbreak air switch(es)
- Secondary current transformers
- Secondary molded case breakers
- Potheads
- Gauges furnished with alarm contacts
- Bolted cover with handhole
|
Standard Tests
Each unit is subjected to the following tests:
- Resistance
- Ratio
- Polarity
- Phase relation
- Core loss
- Exciting current
- Impedance
- Load loss
- Applied potential test
- Induced potential test
- Quality control impulse test
- Pressure leak test
|
|
Request a Quote
Download Brochure
Download Datasheet
|