A critical function of any electricity generation and distribution system is the stepping up or down of voltage at various points in the delivery network. The voltage is stepped up or stepped down at substations using Station Type Transformers. These Station Transformers come in varying sizes, depending on site requirements, but are normally connected to the network through overhead connections which results in exposed HV or LV bushings that necessitate a fence or other protective enclosure for personnel safety and equipment security.
Liquid-filled Transformers Station type (75 to 15000 kVA)
Benefits of Pacific Crest Transformer design
- Compact in size, PCT transformers occupy minimum space
- Robust construction
- Improved cooling for longer insulation life
- Proprietary core clamp/pressure plate design
- Circular coils on mitered cruciform cores for greater fault-withstand characteristics
- Customized designs for both new applications and replacement of existing transformers
- A wide range of features and accessories to satisfy your requirement
Application
- PCT's Station Transformer is the ideal choice for manufacturing facilities, chemical plants, refineries, office buildings, schools, hospitals, shopping centers and more.
- With PCT's high standard of design and manufacturing, you can expect the most exacting paradigms of safety, reliability, functionality and economy
Product Scope
- All voltages up to 138 kV and 450 kV BIL
- Sizes up to 15/20/25 MVA
- Designed for indoor and outdoor applications
- Complete monitoring packages available
Ratings
- kVA ratings - 75 kVA to 15,000 kVA
- Primary Voltage - all voltages through 138 kV - 250 kV BIL
- Secondary Voltage - all voltages through 15 kV
- Frequency - 60Hz
- Temperature rise 65° C
- Consult factory for ratings not shown
Standard Features
- De-energized tapchanger if required
- Secondary spade connectors
- Primary clamp type eyebolt connectors
- Combination drain and sampler (750 kVA and above)
- Pressure test and upper filter press connection - 1" pipe plug
- NEMA two hole ground pad
- Corrosion resistant nameplate
- Provisions for jacking and lifting
- Base suitable for rolling or skidding
- Pressure relief valve
- Rugged steel plate tank reinforced with steel channel selections for strength and rigidity
- Undercoated base
- Door has three-point locking mechanism
- Externally clamped high and low voltage bushings
- Primary compartment accessible only after low voltage door is opened
- 1/2" liquid level plug
- Welded cover with handhole
Optional Features
Five-legged core for wye-wye connections
- 50 cycle
- 55/65° C temperature rise
- High fire point liquid
- Loop feed construction
- Dead front construction
- Lightning arrestors
- Dial type thermometer
- Liquid level gauge
- Pressure vacuum gauge
- Pressure vacuum gauge with bleeder
- Combination drain and sampler
- Pressure relief device
- Bay-o-net fuses
- Weak links
- Current limiting fuses
- Loadbreak oil switch(es)
- Loadbreak air switch(es)
- Secondary current transformers
- Secondary molded case breakers
- Potheads
- Gauges furnished with alarm contacts
- Bolted cover with handhole
|
Standard Tests
Each unit is subjected to the following tests:
- Resistance
- Ratio
- Polarity
- Phase relation
- Core loss
- Exciting current
- Impedance
- Load loss
- Applied potential test
- Induced potential test
- Quality control impulse test
- Pressure leak test
|
|