Home
Products
Solutions
Resource Center
Blog
Careers
About Us
 logo Pacific Crest Transformers -liquid filled distribution transformer
 Search
Resource Center
 
Share/SaveShare/Save Follow UsFollow Us
 
Contact Sales
Ask a Question
Request Quote
 

Grounding Transformer FAQs


Nov, 30 - 2010    Pacific Crest Transfomer


1. What is the purpose for a grounding transformer

 

Simply put, a grounding transformer is used to provide a ground path to either an ungrounded "Y" or a delta connected system and are used to....

  • Provide a relatively low impedance path to ground, thereby maintaining the system neutral at or near ground potential.
  • Limit the magnitude of transient over voltages when re-striking ground faults occur.
  • Provide a source of ground fault current during line to ground faults.
  • Permit the connection of phase to neutral loads is desired.

If a single line to ground fault occurs on an ungrounded or isolated system, no return path exists for the fault current, thus no current flows. The system will continue to operate but the other two un-faulted lines will rise in voltage by the square root of 3 resulting in overstressing of the transformer insulation, and other associated components on the system, by 173%. MOV lightning arresters are particularly susceptible to damage from heating by leakage across the blocks even if the voltage increase is not sufficient to flash over. A grounding transformer provides a ground path to prevent this.

 

2. What is the kVA rating for my grounding transformer?

 

Unless you are using the grounding transformer to provide auxiliary power, there is no kVA rating, because the grounding transformer does not function as a power source. During "normal operation" no current flows in the grounding circuit because the system is balanced and no neutral current occurs. During a fault, the duration is limited to seconds in the extreme and a few cycles in most cases. Some designers talk about a "fault power" rating but this is time sensitive and not a true "kVA" power rating. A grounding transformer will be labeled for grounding use and rated by the continuous current and fault current it is designed to carry.

 

3. What current rating do I need to order my grounding transformer?

 

You need to know the available neutral fault current and duration. This value is needed to calculate the short time heating that results from a fault on the system and should be determined from a engineered system study. Typical values for this range from a few hundred amps to a few thousand amps with duration times expressed in seconds and not cycles. For instance a value of 400 amps for 10 seconds is typical. The fault duration is a critical parameter for the transformer designer. Where protection schemes use the grounding transformer for tripping functions, a relatively short time duration is specified ( 5 -10 seconds). On the other hand, a continuous or extended neutral fault current duration would be required when the grounding transformer is used in a ground fault alarm scheme.

 

4. What is meant by "continuous current"? Are there guidelines for this?

 

You will also be asked to supply the continuous current. You can choose to provide the continuous neutral current or the continuous phase current. This is usually considered to be zero if the system is balanced, however for the purposes of designing a grounding transformer it is a value that is expected to flow in the neutral circuit without tripping protective circuits (which would force the current to be zero) or the leakage current to ground that is not a symmetrical function. Again this value is needed to design for thermal capacity of the grounding transformer. When the continuous current is not known, ANSI/IEEE Std. 32-Reaffirmed 1990 , provides a guideline based on the fault current magnitude. If the value is not specified, the designer will assume the continuous current to be 3% of the short time fault current (based on a 10 second rating)

 

5. Why is the neutral current 3 times the phase current.

 

When an ungrounded system experiences a ground fault event, the grounding transformer provides the return path for the fault currents. The transformer, "sees" this fault current as a zero sequence fault current, meaning it occurs on all three phase simultaneously. In a three phase transformer with equal impedances to ground on all three legs, the current will divide and flow equally in all three phases simultaneously with 1/3 the fault current in each.

 

6. Why is the impedance so critical in my grounding transformer?

 

When current flows in the grounding transformer windings a voltage will be developed by the well known formula ( E = IR) where the resistive component is the impedance. Clearly this is different for every location and application, however we can say that because of the magnitude associated with fault currents, if too high a value is given for the impedance, during the fault the resulting voltage can exceed design limits. It is important to remember that one function of the grounding transformer is to provide voltage support for the faulted leg, thus holding that leg above ground and limiting "neutral shift". In all cases it should be chosen so that the un-faulted phase voltages during a ground fault are within the temporary over-voltage capability of the transformer and associated equipment.

Page: